PAGE 1 BIASI B/40 LINEAR 6-12 SECTION REV. H Please Read Instructions Carefully Save for Future Reference Manufactured by:Manufactured by:Manufactu
BIASI B/40 PAGE 10 Good, reliable operation with a minimum of service starts with attention to the small details: 1. Setting the nozzle position a
PAGE 11 BIASI B/40 BURNER MANUFACTURER Heat WiseBoiler Model B-406 B-407 B-408 B-409 B-410 B-411 B-412Burner ModelSU-3 SU-3 SU-4 SU-5 SU-5 SU-6 SU-6
BIASI B/40 PAGE 12 To check for gas leaks, use a gas detector or apply a soap solution to the joints. DO NOT USE AN Direction of flow Manual Shutof
PAGE 13 BIASI B/40 Piping should consist of: 1. A shut off valve approximately 6’ away from the unit. 2. A 1/8” plugged NPT tapping for gas pressu
BIASI B/40 PAGE 14 The B-40 Linear boiler is a high efficiency unit that requires proper venting. The boiler must be vented to the outdoors by mea
PAGE 15 BIASI B/40 All piping must conform to state and local codes. The supply and return manifolds for B-40 Linear boilers are 2 1/2” male N
BIASI B/40 PAGE 16
PAGE 17 BIASI B/40 NOTE: All piping, boiler controls, gauges and valves must be installed before the jacket has been assembled on the boiler. Refe
BIASI B/40 PAGE 18 1 2 3 4 5 6 7 8 9 1 On/Off Switch 2 Min. Boiler Temp. Thermostat 3 Max Boiler Temp. Thermostat 4 Thermostat By-Pass Button 5
PAGE 19 BIASI B/40 1 2 3 4 5 6 7 8 9 1. On/Off Switch — Turns power to control panel on and off and will disable power to the burner assuming the
BIASI B/40 PAGE 2 Dear Customer: Thank you for buying a Linear commercial boiler. The Linear is a cast iron, oil or gas fired hot water boiler, us
BIASI B/40 PAGE 20 B-40 Control Panel Wiring Diagram for Beckett/Heat Wise Oil Burner 24V CIRCULATOR RELAYBURNER CONTROL
PAGE 21 BIASI B/40 B-40 Control Panel Wiring Diagram for Beckett/Heat Wise Oil Burner Line Voltage CIRCULATOR RELAYBURNER CONTROL
BIASI B/40 PAGE 22 B-40 Control Panel Wiring Diagram for Riello Oil Burner
PAGE 23 BIASI B/40 B-40 Control Panel Wiring Diagram for Heat Wise Gas Burners CIRCULATOR RELAYBurner Primary Control
BIASI B/40 PAGE 24 Check for fouling or soot buildup in the combustion chamber at least every twelve (12) months. Caution: Black carbon soot in
PAGE 25 BIASI B/40 System Checkout: Boiler Model No._________________ Serial No.__________ Original Purchaser: Installer: ____________
BIASI B/40 PAGE 26
PAGE 27 BIASI B/40
BIASI B/40 PAGE 28 ITEM #: B40 REV. H Warranty For BIASI B40 Series Commercial Cast-Iron Water Boilers FIRST YEAR through TENTH YEAR-WARRANTY FOR B
PAGE 3 BIASI B/40 BIASI B-40 Linear Series Section Page Important Information 1 4 General Informati
BIASI B/40 PAGE 4 IMPORTANT INFORMATION Please read this page carefully. ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL
PAGE 5 BIASI B/40 Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon monoxide (CO). Carbon Mo
BIASI B/40 PAGE 6 The Linear series are wet base design, sectional, cast-iron boilers for forced hot water heating systems. The Linear boilers are d
PAGE 7 BIASI B/40 Locate the boiler to provide sufficient clearance for inspection, servicing and maintenance. Minimum clearance to construction or
BIASI B/40 PAGE 8 All Linear series boilers are shipped either as an assembled boiler block or a knock-down boiler block. If the block came unasse
PAGE 9 BIASI B/40 Figure 1:Diagram illustrating the location and function of the front and rear boiler tappings. Boiler Model Length (L) B-40/6 34